Corrigendum A reference is invited to the captioned tender which was floated on January 27, 2020 under the “Tenders” link of RBI website (www.rbi.org.in). In this connection, a Pre-bid meeting was held on February 05, 2020 at 3:00 p.m at 2nd floor Reserve Bank of India, Estate department, Jaipur. The Clarifications in respect of the following points raised by the vendor during the pre-bid meeting are furnished below: Sr. No | Firm’s query | Comments (Revised specifications) | 1 | Firm has asked for carrying capacity of the Hydraulic lift | As mentioned in RFP document | 2 | Firm has asked for required lift speed | Required speed of the lift will be 8-9 mtr/min | 3 | For the carrying capacity of 1 ton, minimum required pit depth should be 600 mm | Pit depth can be increased upto 600 mm depending upon OEM requirement | 4 | Firm has asked for type of doors whether sliding or collapsible to be used. | i) Carriage door should be openable from two sides and closed by MS rails/channels on rest of the two sides. A ramp type arrangement should be provided for openable sides to slide the trolley inside/outside the carriage. ii) Protected wire mesh/cage door should be hinged door with double flaps of equal width and height as per IS norms. iii) All doors are manually operated. | 5 | Firm has asked for the use of the lift | It will be used as freight lift for carrying trollies filled with cash and not for passengers | 6 | | | a) | Firm has suggested a blinking strobe with sound adjustable hooter to indicate that the lift is moving and under operation | A blinking strobe with sound adjustable hooter is to be provided to indicate that the lift is moving and under operation | b) | Firm has suggested electromechanical interlocking for the doors with the landing so that they may not get open until the carriage has reached on landing | An electromechanical interlocking for the doors with the landing so that it may not get open until the carriage has reached on landing | c) | Firm has suggested that Lift should not operate in case of malfunctioning of any of system. | Safety features of hydraulic system should be as per OEM recommendation. Separate indicator for malfunctioning of the system is not required | d) | Firm has sought confirmation whether lift will move in case of overload. Any indication for the same if required will be incorporated separately. | Overload protection should be there as per OEM recommendation. Separate indicatior for the same is not required | e) | Firm has sought confirmation whether lift shaft is protected with MS wire mess on all sides for full height | Remain same as mentioned in RFP document | 7 | | Rest of the specifications will remain same as mentioned in RFP document | This document is considered as part and parcel of the tender and its signed copy should be submitted along with tender document. Reserve Bank of India Jaipur | |