Corrigendum - Supply, Installation, Testing and Commissioning of Microprocessor based Security Alarm System for Bank's Additional Office Building at Nagpur

Minutes of Pre-bid meeting

Supply, Installation, Testing and Commissioning of Microprocessor Based Security Alarm System for Bank’s Additional Office Building at Nagpur

Sr. No. Tender Clause Section reference & page No. Query RBI Clarification
1. Addressable Line Isolating devices Section V(II) h
Page No.51
Whether Addressable Line Isolating Devices are required? Addressable line isolating devices are not required.
2. System should Support long-range radio (LRR) communication. Section V (II) e
Page No.50
Kindly clarify on “system should support long-range radio (LRR) communication System should have the provision of integrating with Bank’s Walkie Talkie system. The required patch panel for this purpose would be provided by the Bank.
3. The master controller shall be Listed for EN / UL / VDS Commercial Fire and Burglary system. Section V (II)
Page No.50
Whether VDS certified system is accepted? As mentioned in section V(II) of Part I of the tender, EN / UL / VDS certified system is accepted. The copy of the certificates should be submitted along with the material.
4. A push button shall be provided for acknowledging the alarm. Section V (II) d
Page No.50
Whether acknowledging the alarm by Single Switch is sufficient? Acknowledging the alarm should be only with password instead of push button.
5. Integration with CCTV System Section V (II) V
Page No.52
Whether security alarm system require to be integrated with existing IPCCTV system? At present no IPCCTV camera require to be integrated with the system. However, system should be capable of integrating IPCCTV system in future, if required.
6.     Whether access control system and BMS system is required to be integrated with the security alarm system? Access control system and BMS is not required to be integrated with the security alarm system but the system should be having provision of integrating access control system in future, if required.
7.     Whether Path indicator is required audio or only flasher lights? Path indicator is required only with flasher lights.
8. Electronic Alarm Sounder Section V (II) IV
Page No.52
What is the output of Electronic Alarm Sounder required? As per section V (iv) of part I of the tender, Electronic Sounder Alarm should be having an output of 90 dB.
9. Master Controller battery backup power Section V (II) h(iv)
Page No.51
What should be the Capacity of the battery for back-up power and make of the battery? As per Sr.No. (iv) of section V(II), the capacity of the battery set shall be sufficient to supply power for the whole system for 48 hours under idle conditions and for at least 2 hours under alarm condition. Battery should be of any one of the make amongst Exide, Panasonic, Amara Raja.
10. Foot operated push button IP-65 degree of protection Page No.57 What type of enclosure is required for foot operated switch? Foot operated switch should be provided with powder coated metal enclosure having IP65 protection to protect from dust and water.
11.     Is there any alarm required against the fault in the equipment / cable etc. In case of cable fault / switch damage, there should be an alarm.